Cooling-water System Optimisation with a Novel Two-Step Sequential Method

Jin Sun,Xiao Feng,Yufei Wang
DOI: https://doi.org/10.1016/j.applthermaleng.2015.01.012
IF: 6.4
2015-01-01
Applied Thermal Engineering
Abstract:In cooling water systems, conventional cooler networks usually operate in a parallel configuration and traditional pump networks consist of pumps which are installed only on the main supply pipeline. However, a series-parallel configuration of coolers can substantially increase the cooling-water return temperature and reduce its flow-rate as well as the efficiency of the cooling tower, but the pressure drop along pipes would increase correspondingly. This paper presents a novel two-step sequential methodology for the optimisation of cooling-water system (CWS). The first step is to use a thermodynamic model to obtain the optimal cooler network. In the second step, the hydraulic model is established to obtain the optimal pump network with auxiliary pumps installed in parallel branch pipes. The proposed model can identify the optimal distribution of cooling water within the network and the optimal installation locations and pressure head of pumps required for CWS. A case study is presented to demonstrate the effectiveness of the proposed methodology. It can save up to 23.3% of the cooler network cost and additional 11% of the pump network cost after optimisation.
What problem does this paper attempt to address?