Study on the Performance of CaSO4 Scale for Phosphorus-Free Modified PEG Scale Inhibitor in Cooling Water System
Huchuan Wang,Jianjun Yang,Chuanrun Li,Mengjie Zhu,Qingyun Wu,Mingyuan Wu,Jianan Zhang
DOI: https://doi.org/10.5004/dwt.2019.23739
IF: 1.1
2019-01-01
Desalination and Water Treatment
Abstract:The static test experiments in this study was conducted to evaluate the inhibiting the formation of calcium sulphate scale. At present commonly in the market used scale inhibitors is commonly phosphorous scale inhibitor, is not conducive to environmental protection. In this paper, synthesized a kind of no phosphorus green scale inhibitor, the scale inhibitor consists of acrylic acid (AA), polyethylene glycol ester (PEGZG maleic anhydride modified polyethylene glycol), allyl sulfonate (SAS) system for the controlled radical polymerization of aqueous phase, through Fourier transform infrared spectrometer (FT-IR) known monomer reaction completely, the best synthetic conditions for AA: PEGZG: SAS = 1: 3: 1 (mass ratio), 6% of the total quality of the initiator to monomer, add and reaction temperature respectively in 70 degrees and 80 degrees, the scale inhibitor in dosing quantity is 5 mg/L, the resistance rate of calcium sulphate scale above 95%, through the simulation of cooling water pipe figure can be concluded that adding scale inhibitors AA/PEGZG/SAS, simulating the circulating cooling water pipes become clear, generating calcium sulphate scale, the scale inhibitor can be used in high hardness water quality conditions, has a certain industrial application prospect.