ICONE15-10174 the Numerical Comparison of Fire Combustion Model and Water-Mist Suppression with Experiments by FDS Code

Hsuen-Nien Li,Yuh-Ming Ferng,Chunkuan Shih,Wen-Sheng Hsu
DOI: https://doi.org/10.1299/jsmeicone.2007.15._icone1510_74
2007-01-01
The Proceedings of the International Conference on Nuclear Engineering (ICONE)
Abstract:FDS [1] code numerically solves a form of the Navier-Stokes equations appropriate for low-speed, thermally driven flow with an emphasis on smoke and heat transport from fires. FDS uses a mixture fraction combustion model. The mixture fraction is a conserved scalar quantity that is defined as the fraction of fuel gas at a given point in the flow field. The model assumes that combustion is mixing-controlled, and that the reaction of fuel and oxygen is infinitely fast. In FDS, Lagrangian particles are used to simulate smoke movement and sprinkling water-mist discharge. In order to evaluate the combustion model and water-mist suppression function of the code, FDS analyses are conducted to simulate two enclosure fire cases available in the literature. Comparisons with other combustion models are also made. For fires suppression by water-mist in FDS, parametric studies are performed to compare various water-mist injection characteristics for maximum suppression. Numerical results indicate that the flame suppression is closely related to characteristics of the water mist, such as droplet diameter, mist injection velocity, injection density. Our present investigations show that the combustion model and water-mist suppression in FDS can provide simulation results that are comparable with the experiments.
What problem does this paper attempt to address?