Exponential Fitting Algorithms for Digitally Recorded HV Impulse Parameter Evaluation

YM LI,J KUFFEL,W JANISCHEWSKYJ
DOI: https://doi.org/10.1109/61.248280
IF: 4.825
1993-01-01
IEEE Transactions on Power Delivery
Abstract:Standard analysis of high voltage impulses comprises determination of parameters describing the recorded impulses. These include peak value, front time, and time to half-value. This paper describes several fitting algorithms intended to facilitate extraction of these parameters from recorded data. These algorithms were used to fit bi-exponential models to smooth lightning and switching impulses, to lightning impulses having oscillatory fronts or peaks where the evaluation of the waveform parameters is based on the construction of a smooth curve, and to tail-chopped lightning impulses. The overall effectiveness of these algorithms and their influence on parameter estimates are presented and discussed.
What problem does this paper attempt to address?