Impacts of Bad Data on the PMU Based Line Outage Detection

Xuan Liu,Zhiyi Li,Zuyi Li
2015-01-01
Abstract:Power systems become more prone to cyber-attacks due to the high integration of information technologies. In this paper, we demonstrate that the outages of some lines can be masked by injecting false data into a set of measurements. The success of the topology attack can be guaranteed by making that: 1)the injected false data obeys KCL and KVL to avoid being detected by the bad data detection program in the state estimation; 2)the residual is increased such that the line outage cannot be detected by PMU data. A quadratic programming problem is set up to determine the optimal attack vector that can maximize the residual of the outaged line. The IEEE 39-bus system is used to demonstrate the masking scheme.
What problem does this paper attempt to address?