HI-13 tandem accelerator radiation protection system

Xiaofei Wang,Yueming Hu
2011-01-01
Abstract:After more than 20 year's operation, the radiation protection system of HI-13 Tandem Accelerator laboratory needs to be upgraded in order to provide for higher personnel protection reliability, more convenience of worker's operations and farther display integrity of the working states. This new radiation protection system compose of seven protective doors control units and seven emergency door-open buttons , 23 groups of states indicators, 17 groups of alarms, 17 groups of workshopempty units , L.E Faraday cup and IMAG Faraday cup, as well as computer control and display system based on PLC. Pre-empty section is prerequisite before close the protective doors to ensure nobody be exposed irradiation environment otherwise the door-open would be disabled. Even thought somebody left, pushing nearby alarm button and inner emergency door-open button will induce glittery signal and simultaneous door-opening. L.E Faraday cup and IMAG Faraday cup execute immediate beam interruption once accidence occurred. The enough distributed indicators indicate the real time states of all the work fields. All the above devices and units are interlocked follow some complex but logical protective rules. In addition, computer workstation is built supported by radiation protective programs. Accordingly, after full information and operation action signals are collected and transferred to it, this computer workstation can complete full-sides status monitoring and provide convenient control and display interfaces as well as pop adequate prompt frames. Copyright © 2011 by IPAC'11/EPS-AG.
What problem does this paper attempt to address?