Study On Fault Indicative Features In The Automated Fault Detection And Diagnosis (Fdd) For Chillers

H. Han,B. Gu,T. Wang,Z. R. Li
2011-01-01
Abstract:The benefits of applying automated fault detection and diagnosis (AFDD) to chillers include less expensive repairs, timely maintenance, and shorter downtimes. This study employs feature selection (FS) techniques, genetic algorithm (GA) based wrapper, to search for the fault indicative features in data driven chiller FDD applications, so as to improve FDD performance while saving computation time and initial sensor cost. The results show that the eight features, centered around the core refrigeration cycle and selected by the GA-SVM wrapper from the original 64 features, outperform the other three feature subsets by the GA-LDA (linear discriminant analysis) wrapper, with an overall classification correct rate (CR) as high as 99.53% for the 4,000 test samples randomly covering the normal and seven typical faulty modes. The CRs for the four cases with FS are all higher than that without FS (97.45%) and the test time is much less, about 28 similar to 36%.
What problem does this paper attempt to address?