Experimental Study on the Effect of Elliptical Inlet Nozzle on Performance of Multi-Blade Centrifugal Fan

Xuanfeng WEN,Xin YANG,Datong QI,Yijun MAO,Wangming CHEN
2011-01-01
Abstract:Forward-curved multi-blade centrifugal fans are widely used in central air conditioning systems. In this study, a new elliptical inlet nozzle in a multi-blade fan was designed, and experiments were conducted to investigate the effects of this structure on the fan performance. The results show that properly enlarging outlet area of the inlet nozzle will increase the aerodynamic performance of the fan but lead to greater A-weighted sound pressure level (SPL). Compared with the conventional inlet nozzle, the elliptical inlet nozzle with reasonable parameters and installation position can improve the aerodynamic performance. When the eccentricity angle θ was 0°and the eccentricity ratio, ε1 or ε2 was 0.067, the fan volume flow rate and the total efficiency increase by 8.8%-12.8% and 1.7%-4.6%, respectively, while the A-weighted SPL decrease by 0.4-0.6 dB. Moreover, the fan volume flow rate and the total efficiency increase by 2.5%-6.0% and 0.6%-1.4%, respectively, while the A-weighted SPL decreases by 1.2-1.5 dB when θ was 30°and ε1 or ε2 was 0.067. This experimental study may provide an approach for improving the multi-blade fan performance.