Function of Insulators in the Dynamic Analysis of Transmission Line System

SHEN Guo-hui,YUAN Guang-hui,LOU Wen-juan,SUN Bing-nan
DOI: https://doi.org/10.3785/j.issn.1008-973x.2011.11.012
2011-01-01
Abstract:A methodology to change the lengths of insulators in the dynamic analysis was employed to investigate the function of the insulators.The finite element models of transmission line with and without insulators were built.The difference of vibration characteristics between the models with and without insulator was analyzed.The function of insulators on along-line responses of transmission line system was investigated using ice shedding analysis and the function of insulator on along-line and cross-line responses was investigated using seismic analysis.Results show that the swing of the insulators has significant effect on the reduction of unbalanced longitudinal forces induced by ice-shedding impact.And if the length of the insulators is longer,the effect of reduction will be better.In seismic analysis,the insulator has significant effect to reduce the responses in the along-line direction and has insignificant effect on the responses in the cross-line direction.The discrepancy will be introduced in the dynamic analysis of transmission line system if a calculating model without insulators is used.