High Precision Detection of Fundamental of Power Grid Based on Back Propagation Neural Network

王勇,付志红,张淮清,王好娜,侯兴哲
DOI: https://doi.org/10.13335/j.1000-3673.pst.2011.08.007
2011-01-01
Abstract:Fundamental of power grid is an important index for electric energy metering and power quality evaluation. A high-precision detection approach, which is based on back propagation neural network (BPNN), for the frequency and amplitude of power grid fundamental is proposed. It is derived mathematically that the relationship of the time difference, which is between zero-crossing point of sinusoidal signal and the intersection point of time axis and the line connecting two symmetric points on signal curve at both sides of the zero-crossing point, to signal frequency is not strictly linear but monotonous, and the relationship is independent of the amplitude of the signal. Accordingly, the mapping relation between the time difference and fundamental frequency is built by BPNN. Results of simulation by Matlab show that using the proposed algorithm the detection accuracy of fundamental frequency is 10-4 and the detection accuracy of fundamental amplitude is as high as 10-5, and these detection results are sharply higher than those by interpolation algorithms based on fast Fourier transform (FFT) and Hamming window; random noise and harmonics slightly influence the measuring accuracy by BPNN, so the proposed algorithm possesses strong anti-interference capability.
What problem does this paper attempt to address?