Electromechanical Transient Modeling and Simulation of Direct-Drive Wind Turbine System with Permanent Magnet Synchronous Generator

高峰,周孝信,朱宁辉,苏峰,安宁
DOI: https://doi.org/10.13335/j.1000-3673.pst.2011.11.011
2011-01-01
Abstract:Based on vector decoupling control strategy,an electromechanical transient model of direct drive permanent magnet synchronous generator(PMSG) system,in which the structure of twin back-to-back converters is utilized and the most common space vector decoupling control scheme is adopted,is built.The built model is suitable for power system transient stability analysis.Two reasonable hypotheses for the built model are made: active power and reactive power are fully decoupled during the transient process and the measured electrical quantities are accurate and fully equal to actual ones.According to the hypotheses and based on real physical facility,the electromechanical transient model of direct drive PMSG is simplified,meanwhile dynamic process of PWM converter's DC voltage and the operating characteristic of low voltage ride through are taken into account.Simulation results show that dynamic response of the built model is basically consistent with that of electromagnetic transient model,thus owing to the reasonability and accuracy of the built model it can be used to analyze the impact of grid-connected large-scale direct drive permanent magnet synchronous generator(PMSG) system on security and stability of power grid.