Transient Voltage Stability of Independent Electric Power Systems with Induction Motors

WANG Yihong,ZHANG Xuemin,SUN Yujiao,MEI Shengwei
DOI: https://doi.org/10.16511/j.cnki.qhdxxb.2011.01.002
2011-01-01
Abstract:Independent electric power systems having induction motors can experience voltage stability problems.A multi-motor,multi-generator power system model was used to analyze transient voltage stability.This model effectively eliminates the zero eigenvalue of the Jacobi matrix at the equilibrium point,while guaranteeing equivalence with the original system using a purely differential equation model.A method to differentiate transient voltage in stabilities from transient angle in stabilities was presented,which is used for engineering design.Finally,a transient angle stability margin index based on semi-tensor product was extended to the transient voltage stability problem.Simulations show that the analysis method can effectively evaluate the transient voltage stability of independent electric power systems and predict reasonably accurate critical clearing times.
What problem does this paper attempt to address?