Cooling performance analysis of radiant panel at different positions

Zhihong Gao,Xiaohua Liu,Yi Jiang
DOI: https://doi.org/10.3969/j.issn.1003-7985.2010.02.049
2010-01-01
Abstract:The influence of the panel position on the cooling performance of a radiant panel is analyzed.The coupled simulation of convection and radiation is set up by a computational fluid dynamics(CFD) method.The simulations with different panel positions and different indoor heat sources are used to calculate the cooling capacity of the radiant panel and the indoor thermal environment.The simulation results are in good agreement with the experimental results.The results show that when the indoor heat source temperature is low,the convective heat flux is the main influence factor of the cooling capacity and the radiant panel should be placed on the wall or on the ceiling.Otherwise,when the indoor heat source temperature is high,the radiation heat flux is the main factor and the radiant panel should be placed as near to the heat sources as possible.