Adequacy Evaluation of Transmission Systems Using Monte Carlo Simulation and Nonlinear Programming Technology

Xin ZHOU,Ming-bo LIU,Min XIE
DOI: https://doi.org/10.3969/j.issn.1674-3415.2010.20.009
2010-01-01
Abstract:The non-sequential Monte Carlo simulation algorithm is applied to sample failure states of transmission systems,and network topology analysis is realized by means of the storage based on connection matrix and breadth first search techniques so that multiple failures and islanding are identified efficiently and sampling time of failure states is reduced.Also an optimal load shedding non-linear programming model is estabilished which is solved by primal-dual interior point algorithm.Futhermore,the severe failure states are filtered and sorted through weighting the sampling probability of failure states and optimal load shedding quantity to find out operational risks and weaknesses of transmission systems.The correctness and effectiveness of the proposed method have been verified on IEEE-RTS system.
What problem does this paper attempt to address?