Impact analysis of energy-saving dispatching on the frequency and line losses of large receiving-end grid

Hong-mei LI,Zheng YAN,Yi LIN,Kai NIU
DOI: https://doi.org/10.3969/j.issn.1674-3415.2010.20.044
2010-01-01
Abstract:Taking special case of thermal-power and large receiving-end of Shanghai power utility as examples, the negative impact on system configuration, load flow and safety operation is analyzed from current energy-saving dispatching and generation units optimal combination implemented by the priority level of energy-saving and emission reduction. Based on the analysis of some questions existing in energy-saving dispatching of power system, BPA software is applied to do simulation, and results show that in the region where power is supplied by mostly thermal power, if all generation units are sequenced according to the priority level complying with the code of Energy Conservation, Power Generation and Distribution, although coal consumption and pollutant emission can be reduced, the increasing of line loss and frequency fluctuation cannot be avoided, so that, economical efficiency and stability of power system will be disturbed to some degree.
What problem does this paper attempt to address?