Study on current loop control error in shunt power quality controller

Guopeng Zhao,Jinjun Liu
2010-01-01
Abstract:In practical applications of shunt power quality controllers with direct current control, very often a quite significant command-tracking error exists in the current control loop while the actual output current of the converter is still satisfactory. Analysis and design considerations were carried out to investigate this confusing issue. The control error is caused by the influence of the source voltage. The error is an active current. The current tracking error produces over-shoot current in the dynamic process. A method of discharging the DC side voltage was presented to suppress the over-shoot current. Both simulation investigations and hardware experimental results were finally provided to verify the analysis and specification. Based on the conclusions, the understanding of the current loop is more clearly, and the design of the current loop is more optimal. © 2010 Chinese Society for Electrical Engineering.
What problem does this paper attempt to address?