Coordinated Automatic Generation Control with Voltage Security Constraints for Interconnected Power Grids

杨方,孙元章,程林
DOI: https://doi.org/10.3969/j.issn.1006-6047.2010.08.003
2010-01-01
Abstract:A two-level supervisory control mode based on model predictive control is proposed for EDC/LFC.The upper controller provides the reference trajectory for lower controller according to the real-time system status.With modal analysis technique,the reactive power adjustment cost model is established for the cooperated control of voltage with AGC.The lower controller is for the optimal load frequency control,which transforms the original lagged control into model predictive control.The optimization model is established based on the short term load forecast,which can be solved by linear model predictive control to realize the economic assignment of unit adjustment with the CPS criterion satisfied and to reduce the overshoot and frequent operation.The effectiveness of proposed control mode is validated by the case study for New England 10-generator 39-bus system.
What problem does this paper attempt to address?