EXPERIMENTAL STUDY ON SOLAR AND AIR SOURCE HEAT PUMP INTEGRATED SYSTEM WITH TRIPLE-SLEEVE ENERGY STORAGE EXCHANGERS

Lingyan Yang,Long Ni,Yang Yao,Zuiliang Ma,Yiqiang Jiang,Quan Zhou
DOI: https://doi.org/10.19912/j.0254-0096.2010.09.017
2010-01-01
Abstract:An experimental table was built to verify the feasibility of solar and air source heat pump integrated system with triple-sleeve energy storage exchangers based on the characteristics analysis of it in this paper. Experimental data show that the COP of integrated system is between 2.0 and 2.8 in direct expansion cold storage mode, between 3.00 and 3.75 in heating mode using heat storage, between 3.31 and 3.45 in heat and release mode. So the feasibility of the integrated system is proved by the experiment results, the new integrated system can work efficiently and safely in different modes.
What problem does this paper attempt to address?