HEAT PUMP TYPE BCCHP SYSTEM BASED ON SOFC

Xiling Zhao,Lin Fu,Shigang Zhang
DOI: https://doi.org/10.3321/j.issn:0254-0096.2009.11.010
2009-01-01
Abstract:Nowadays, the energy consumption of the Building Combined Cooling, Heating and Power system( BCCHP) is higher comparatively because that the lower efficiency of the power generation device or the inappropriate use of waste heat. A heat pump type Solid Oxide Fuel Cell(SOFC) Building Combined Cooling, Heating and Power system was put forward aimed at the situation, which uses the SOFC as power generation device and uses the absorption heat pump to recover the latent heat of waste heat. The system's operation principle and schematic configuration was introduced, and the system' s performance is studied through the modelling and simulation of different facilities in the system. A case study is done based on a 80kW consumer, and it is shown that, the electric efficiency and thermal efficiency could be 46.3% and 51.9% in winter and the electric efficiency and cooling efficiency could be 46.3% and 51.9% in summer on the design condition, that is, the comprehensive efficiency of heat pump type SOFC-BCCHP system is improved com-pared with conventional BCCHP system. The system makes up the deficiency of conventional system, and it is the inte-gration of high efficiency energy conversion type with high efficiency energy utilization method. The research work has the significance of energy utilization ratio and environment quality improvements.
What problem does this paper attempt to address?