Numerical Simulation of Fire Pump's Transient Performance During the Staring Period

陈铁军,邵杰,董金新,刘树红
2009-01-01
Abstract:The fire pump,widely used in public places,is typically adopted by the fire-extinguisher system of fire hydrant and automotive spilling.Quick start of the pump is of crucially importance to the fire extinction application.To study the hydraulic transient of the starting stage,a centrifugal fire pump was experimentally tested,and a large eddy simulation(LES) was carried out.This paper shows that,the LES simulated variation trends of pump head and rotational speed with time at the starting stage agree well with the measurements,and the transient effects are also fairly well predicted.Thus LES is a suitable method for simulation of the dynamics of fire pump starting.
What problem does this paper attempt to address?