Effect Of Airspeed On Removal Performance Of Particles In An Ufad Room

Can Li,Nianping Li
2009-01-01
Abstract:Air flow is delivered to the occupied region directly from the floor in under-floor air distribution system. Particle entrainment by supply airflow plays an important role in indoor particles. However, the effects of air speed on indoor contaminant particle concentration have not been well characterized. In this paper, a physical and numerical model was established to simulate the airflow field and particle tracks by using the Lagrangian method. Experiments were performed in a full-scale small chamber under four airspeed (0.21-7.6m/s) conditions. The size-resolved (0.1-10 mu m) particle concentration decay rates were measured. Experiments results showed that the indoor particle concentration decay increases with the mean airspeed, and larger particles exhibit greater effects than smaller particles. Furthermore, the re-suspension life of particles exhibits a large dependence on airspeed and size: it decreases more strongly with increased indoor airspeed of particles above 3 mu m than those below 1 mu m. The calculations agree well with the experiments tendency.
What problem does this paper attempt to address?