An Active Low Voltage Ride Through Strategy of DFIG-based Wind Turbine Using Stator Series Impedance
ZHANG Chen,LI Zheng,CAI Xu,WANG Ningbo,DING Kun
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2015.12.004
2015-01-01
Abstract:For double-fed induction generators (DFIGs) low voltage ride through (LVRT) issues, research achievements are mainly divided into two categories: when suffering from small values of the grid voltage drop, the low voltage operation capability can be strengthened through optimized control strategies to ensure uninterrupted operation of DFIG; when grid voltage drop value is large, the rotor converter should be bypassed by rotor crowbar, the tripping action can be avoided and DFIG stay connected during grid faults, in the mean while the grid-side converter operates in the STATCOM mode for grid voltage support. As for large value grid voltage drop, LVRT with the rotor crowbar are considered to be a passive measurement, DFIG behaves like an induction machine or a generator depends on its slip and absorbs certain reactive power during grid faults, which is not conducive to grid voltage recovery. To overcome this drawback, a stator series impedance based active LVRT strategy was proposed, uninterrupted operation of DFIG during grid faults is achieved, and a nearly rated reactive current can be injected into grids through the rotor-side converter, which is conducive to grid voltage recovery. Besides, a robust fault operation capability of DFIG is obtained through optimizing the value of the series impedance and controller parameters.