Abstract:In order to resolve the hazard of biofouling and scale in circulating cooling water system of power stations, this paper takes the lead in combining high-voltage pulses and high-frequency pulses for sterilization and descaling process. It analyzes both electromagnetic effects and biochemical effects on sterilizing and descaling process caused by the high-voltage pulses and high-frequency pulses respectively. The pulse generator is designed according to the requirements of electromagnetic parameters for effective operation. The design and improvement of process chambers are assisted by electromagnetic field simulation technology. Experimental data prove that the system can output high-voltage pulse whose maximum peak value reaches 7 kV and high-frequency pulse whose maximum peak value reaches 100 V the frequency ranges from 500 kHz to 2 MHz. The rate of sterilization can be as high as 91%,and the rate of descaling reaches 71%. This system is expected to achieve the standards of industrial water treatment through further research.