Analysis of a Time-varying Power Component Outage Model for Operation Risk Assessment

NING Liaoyi,WU Wenchuan,ZHANG Boming
DOI: https://doi.org/10.3321/j.issn:1000-1026.2009.16.002
2009-01-01
Abstract:A time-varying and condition-based component outage model is needed for operation risk assessment, which should consider the change of weather, aging degree and other operation conditions. Various existing definitions of the failure rate, the hazard rate and their relation are well analyzed. The relationship between the failure rate in Poisson process model and the state transition rate in Markov process model is presented. The conditions and the method to formulate component outage models using Markov process in time-varying condition are introduced. Based on the above research, in can be concluded that Markov model is fit for overhead transmission lines and the non-Markov model must be used for transformers. Finally, two different time-varying component outage models for overhead transmission line and transformer are developed respectively. The numerical examples are also presented. This work is supported by Special Fund of the National Basic Research Program of China (No. 2004CB217908) and National Natural Science Foundation of China (No. 50707013). ©2009 State Grid Electric Power Research Institute Press.
What problem does this paper attempt to address?