Clustering Analysis in Condition Assessment Factor Classification of Circuit Breaker

Guo-gang ZHANG,Yu LI,Xiang TANG,Ying-san GENG
2008-01-01
Abstract:A method based on the fuzzy theory is introduced for condition assessment of high voltage circuit breaker. By this means, the condition-affected factors are classified using the fuzzy cluster analysis. The process is in the following: First, the main factors for assessing the condition of the high voltage circuit breaker are selected and abstracted, according to circuit breaker type such as SF 6, oil and vacuum circuit breaker. Second, a fuzzy similar matrix is constructed using those factor items. Based on resolution structure of fuzzy equivalent matrix, a fuzzy equivalent matrix is worked out. Thirdly, dynamic clustering analysis is realized, with calculating sectional sets of the fuzzy equivalent matrix under different threshold conditions. Then a hierarchical model of fuzzy comprehensive condition assessment for high voltage circuit breaker is made up. Finally, the weights of those factors are calculated by the method of the fuzzy analytical hierarchy process. The process of dynamic clustering, judgment set selecting and hierarchy of the factors calculating for SF 6 high voltage circuit breaker are given in detail. Also, a sample of circuit breaker is analyzed to prove that assessment factors classification method of high voltage circuit breaker based on fuzzy cluster analysis is rational and effective.
What problem does this paper attempt to address?