Experimental Study on Explosion Limits of a New Alternative Refrigerant

HONG Rong-hua,CHEN Qi,CHEN Guang-ming,ZHANG Rui
DOI: https://doi.org/10.3785/j.issn.1008-973x.2008.04.033
2008-01-01
Abstract:An experimental apparatus for testing the explosion limits of flammable refrigerants was established following the standard of American Society for Testing Materials(ASTM) E681-01.Factors affecting the explosion limits of refrigerants were analyzed.Experimental results show that the physical characteristics of HFC-161/125/32 are similar to those of HCFC-22,its ozone depleting potential(ODP) is zero,and its global warming potential(GWP) is smaller than that of HCFC-22,therefore the new refrigerant HFC-161/125/32 can be considered as a promising alternative refrigerant to HCFC-22.The explosion limits of the flammable binary refrigerants of HFC-161/125/32 systems were tested.Based on the experimental data,the critical flammability line of the mixtures HFC-161/125/32 was plotted.Analysis result shows the importance of explosion limits to the safety of flammable refrigerants in manufacture and application.
What problem does this paper attempt to address?