Emergency Support Cooperative Control and Vibration Attenuation of a Power System

TANG Honghai,LI Chunwen
DOI: https://doi.org/10.3321/j.issn:1000-0054.2008.01.036
2008-01-01
Abstract:A continuous switching control algorithm in a buffer region on one side of the switch line was developed to attenuate the chatter and impact resulting from bang-bang switching time optimal control. A feedback controller was then developed for a non-affine nonlinear model of power systems including a static var compensator (SVC) using the inverse system method. The controller was a time optimized emergency support cooperative control strategy. The control strategy was simulated in a single machine infinite bus system with initial errors and three-phase short circuit faults. The simulation results show that the control strategy can eliminate chattering in a closed system and effectively reduce the impact during the switching of control laws, thus achieving the time optimized response and verifying the potential practical value of the control algorithm.
What problem does this paper attempt to address?