Dc-link voltage control of full power converter for wind generator operating in weak grid systems

Xibo Yuan,Fred Wang,Rolando P. Burgos,Yongdong Li,Dushan Boroyevich
DOI: https://doi.org/10.1109/APEC.2008.4522807
2008-01-01
Abstract:In this paper, permanent magnet wind generator with full power converter is investigated in weak grid systems, where the dc-link voltage needs to be controlled from the generator side instead of grid side. When wind power takes a large portion of grid power, it needs to help grid to regulate the voltage and frequency. To achieve this, a variable step search algorithm based on the derivation of the electro-mechanical dynamic model describing the wind turbine is proposed,which enables the wind generator output power to match the load power, thus keeping the dc-link voltage regulated. Based on the non-linearity and different slopes of wind power curve, the controller is designed specifically for different sectors. A back-EMF observer based sensor-less generator control is adopted here to regulate the generator speed. Simulation is built up with a 10kW wind power generator system and a reduced-scale 1.5kW system experiment is also carried out in the condition of load power step change and wind speed change. Both simulation and experimental results validate the effectiveness of - the,proposed control scheme, where the dc-link voltage can-be kept stable by adjusting the wind generator speed.
What problem does this paper attempt to address?