Two-layer zonal modeling of smoke movement in single fire room

Yan Tong,Mingheng Shi,Jiapeng He
DOI: https://doi.org/10.3321/j.issn:1001-0505.2008.03.017
2008-01-01
Abstract:In indoor fire's two-layer zonal modeling, the variation of indoor pressure should be considered. The first law of thermodynamics is utilized to derive a set of ordinary differential controlling equations in which indoor gas parameters changes with time. These equations are stiff, but a Gear algorithm can be adapted to it. Based on the selected Heskestad plume model, the time-dependent variation regularity of pressure differences between indoor and outdoor, smoke heights, upper layer smoke temperatures, and lower layer air temperatures have been calculated for a single fire room with floor areas and mechanical exhaust smoke rates of 49 m 2, 0.3 m 3/s; 49 m 2, 0.4 m 3/s; 100 m 2, 0.3 m 3/s; 100 m 2, 0.4 m 3/s respectively. Results show that pressure difference changes with time quickly; Heskestad and Mcaffrey plume models have a better similarity; Decreasing of smoke height and increasing of upper layer smoke temperatures are influenced more by floor areas than by top exhaust smoke rates.
What problem does this paper attempt to address?