Study on High Voltage and Large Capacity Vacuum Interrupters

Junhui Wu,Jing Yan,Hongfei Zhao,Zhiying Ma
DOI: https://doi.org/10.1109/icpst.2006.321497
2006-01-01
Abstract:Because of great harmfulness for greenhouse effect, SF6 gas has to be limited. It is necessary to develop high voltage vacuum circuit breaker to replace SF6 circuit breaker. Insulating structure and arc characteristics of vacuum interrupter are the key. For 72.5 kV vacuum interrupter, impulse voltage test is carried to find out factor of effecting on its insulating performance and insulating structure is improved. As a result, a design of 126 kV vacuum interrupter is presented and electric field distribution is calculated. Based on statistical property of breakdown in high voltage vacuum interrupter, its voltage withstand capability is analyzed. The relation between arc voltage and arc current, the influence of gap distance on arc noise is measured on 72.5 kV vacuum interrupter and the experimental results are analyzed.
What problem does this paper attempt to address?