Dynamic Response of Fan Coil Unit Performance Caused by Exterior Disturbance

ZHEN Wei,GU Bo,BIAN He-jie,LI Yuan-guang
DOI: https://doi.org/10.3321/j.issn:0367-6234.2007.01.039
2007-01-01
Abstract:A heat and mass transfer model between air and water of fan coil unit is introduced and is solved by concept of equivalent dry running condition,which transforms wet running condition to dry running condition to simplify the calculating process by excluding the dehumidifying coefficient.With a stationary distributed parameter model,the running characteristics under steady condition are simulated.Based on the steady simulation,with a lumped parameter model,the dynamic process of performance variety between one steady state to the next is simutated.With the same disturbance,the temperature of inlet water affects the performance of fan-coil more strongly than temperature of inlet air.
What problem does this paper attempt to address?