A New Method to Calculate the Steady-State Temperature Field and Ampacity of Underground Cable System

Yongchun Liang,Yanming Li,Jinai Chai,Zhenggang Wang,Zhongkui Li
DOI: https://doi.org/10.3321/j.issn:1000-6753.2007.08.034
2007-01-01
Abstract:Based on convection of ground surface and temperature of soil deep under the surface unchanged, open domain temperature field of underground cable system is equivalent to close domain temperature field. Finite element method (FEM) is used to calculate the temperature field of underground cable system given load current. Loss in cable sheath is attributed to cable conductor based on thermal circuit method. The thin layer of cable is handled by harmonic mean method, and the cable is equivalent to two layers, conductor and outer layer. Number of FEM nodes is reduced. Accuracy and rate of calculation is improved. Ampacity of underground cable system is calculated by subtense truncation approach. The results of test and calculation show that FEM is effective to calculate the temperature field and ampacity of underground cable system in engineering.
What problem does this paper attempt to address?