Fast Detection Algorithm Based on Curve Fitting Algorithm for Custom Power Device
LIU Bing,RUAN Jiang-jun,LUO Xiang,YUAN Xiang,YU Shi-feng
DOI: https://doi.org/10.3969/j.issn.1006-6047.2007.09.013
2007-01-01
Abstract:The key technique in the development of power custom devices,which can effectively compensate voltage sags and short interruptions,is the quick detection of voltage sags and short interruptions in 3 ms.Based on the study of different detection algorithms used in protects,such as virtual value algorithm,imperfect voltage algorithm,derivative algorithm,three phase d-q decomposition algorithm,60-degree-delay dummy three phase d-q transform algorithm and differentiate dummy three phase d-q transform algorithm,a fast detection algorithm is presented based on curve fitting.Both two-point curve fitting algorithm and three-point curve fitting algorithm are researched.After comparing all these detection algorithms,it is concluded that,the two-point curve fitting algorithm is the most practical for power custom devices.Simulation of voltage sag processing by different algorithms on DSP proves the conclusion.
What problem does this paper attempt to address?