Refrigerant migration characteristics of R410A split air-conditioning system

Yuanming Zhang,Xiaokui Ma,Guoliang Ding
2006-01-01
Abstract:In order to study the start-up and shut-down characteristics of R410A split air-conditioners under cooling mode, the refrigerant distribution in the system as well as temperatures and pressures at the suction and discharge point were measured during first 30 min at start-up and shut-down, respectively. It is found that the existence of accumulator puts off the stabilization of the system at start-up so that it takes about 5 min for the system to get steady. During the start-up, the ratio of refrigerant inventory in condenser to the whole inventory in the system increases from 17% to 44%, while that of the evaporator decreases from 36% to 14%. The existence of receiver puts off the stabilization of the system at shut-down so that it takes about 15 min for the system to get steady. During the shut-down, the ratio of refrigerant inventory in condenser to the whole inventory in the system decreases from 61% to 22%, while that of the evaporator increases from 19% to 51%.