FEM Analysis of the Inductance Parameters in a Large Hydro-Generator with Eccentricity

ZHU Jiahui,QIU Arui,SUN Yuguang
DOI: https://doi.org/10.3321/j.issn:1000-0054.2006.01.004
2006-01-01
Abstract:Some eccentricity always exists in hydro-generators which results in changes of the air gap magnetic field and influences the generator operation.The effect of the eccentricity can be analyzed by modeling the generator.A 2D finite element method(FEM) was used to model the magnetic field distribution with the eccentricity,self-inductance parameters and mutual-inductance parameters included.Comparison of the inductances calculated using the FEM and the magnetic conductance method showed that the inductance in the stator winding branch or between the stator and the rotor winding branch in the hydro-generator are no longer symmetrical because of the eccentricity.Both the inductance in the stator winding branch where the air gap is smallest and the mutual inductance between this stator winding branch and the rotor winding branch will increase,while the inductances in the opposite direction will decrease.
What problem does this paper attempt to address?