Numerical Calculation of the Corona Loss of the HVDC Transmission Lines
YIN Han,ZHANG Bo,LI Min,LIU Lei,HE Jinliang
DOI: https://doi.org/10.3969/j.issn.1003-6520.2013.06.007
2013-01-01
Abstract:Due to the influence of space charges around conductors,it is very complicated to calculate the corona loss of high-voltage direct-current(HVDC) transmission lines.Thus,in engineering designs,various empirical formulas are adopted to estimate the corona loss,which lacks universality.Therefore,on the basis of a numerical analysis of the ion flow field around HVDC transmission lines,we analyzed the rationality of three methods for calculating corona current,i.e.the Shockley-Ramo method,integration around conductor,and integration around calculation boundary.The analysis shows that,when the Shockley-Ramo method and integration around conductor method are adopted,the calculation results are close to the measurement results.However,the Shockley-Ramo method uses all the space charges to calculate corona current,while the integration around conductor only uses the charges around conductor.In numerical calculations,the Shockley-Ramo method has better universality,and can calculate the corona loss of the HVDC transmission lines fast,stably,and accurately,providing reference for engineering designs.