SIZES OPTIMIZATION ON CROSS-FLOW DEHUMIDIFIER USING LIQUID DESICCANT

Xiaohua Liu,Yi Jiang,Kaiyang Qu
DOI: https://doi.org/10.3321/j.issn:0254-0096.2006.09.004
2006-01-01
Abstract:Based on the experimental test and theoretical model of the cross-flow dehumidifier using liquid desiccant, optimization method was proposed for cross-flow dehumidifier, considering pressure drop and the combination of heat and mass transfer performances at the same time. The results showed that the optimizing dimensions of the cross-flow dehumidifier before and after optimization are 500 × 500 × 1200 mm3 and 650 × 310 × 1050 mm3, respectively for the air flow rate of 3600 m3/h, Good performance was realized for the optimized cross-flow dehumidifier. Compared to the original de-humidification module, the volume decreases to 70% and pressure drop decreases to 49%, while the enthalpy and moisture efficiencies are almost the same.
What problem does this paper attempt to address?