A Feed Water Control Method with Gray Treatment for Drum Boilers

YU Nan-hua,SU Ming
DOI: https://doi.org/10.3969/j.issn.1674-7607.2005.06.021
2005-01-01
Abstract:Three tough problems are involved in the triple cascade control of water level in a boiler drum,i.e.the seeming water level,signal noise and mismatched control parameters.According to analysis,it is necessary that a differentiating procedure be added,which can alleviate the seeming water level problem,but requires a certain treatment.To solve the remaining two problems,it is proposed to use gray prediction for the reduction and control of signal components that match the control models' parameters,and to use compensation control and self-adaptive algorithm to solve the noise problem and that of mismatching control parameters.Simulation results show that a feed water cascade control system with differentiating property,following a gray treatment,exhibits better control properties than conventional cascade feed water control systems.Figs 9 and refs 11.
What problem does this paper attempt to address?