Investigation on Steady State Characteristics and Loss Reduction Measures of 220 Kv Power Cables
Ligang Zhang,Lifeng Qui,Enzhe Wang,Hanshan Zhu,Xiaofan Huang,Xiangrong Chen
DOI: https://doi.org/10.1007/978-981-99-1439-5_27
2023-01-01
Abstract:With the rapid development of urbanization in China, power cables have gradually occupied the main position in the urban network, and the loss caused by the power cables in the power transmission has also continually increased. In this paper, the node admittance matrix of a power cable system is firstly constructed based on transmission line theory, thereafter an accurate method for solving the steady-state model of cable system is proposed. Introducing an additional series impedance at the cable joint can have a good loss reduction effect. By comparing the series resistance and reactance for the cable loss reduction characteristics, it is found that the series reactance has better loss reduction characteristics. Compared with the initial loss, when the series reactance value is 10 Ω, the total loss of the power cable is reduced by 88.97%, and no active power is generated. The power loss can be further reduced by the combination of the impedance amplitude and the phase angle. When the impedance is less than 2 Ω, its phase angle should be 60°, and if the impedance is more than 2 Ω, the phase angle should be 90°.