Abstract:To overcome the shortcoming of the conventional process monitoring methods' assumption that the extracted features must be subject to multivariate normal distribution, a novel method based on independent component analysis (ICA) and principal component analysis (PCA) was presented for process performance monitoring by using a two-step procedure. Step I: Process operating information with non-normal distribution was extracted by means of ICA, and the density function of this part of the information was estimated by means of Parzen density estimator for calculating the confidence limits; Step H: The information with normal distribution was extracted from the underlying residual datasets by PCA, and the confidence limits were determined for Q and Retelling T2 statistic. With the advantage that no assumption of normal distribution on process datasets is needed, application of the proposed method to a double-effect evaporator yielded has less missing alarms than the conventional process monitoring methods.