Influence of SO4 2- and Cl- the corrosion behavior of copper tube in air-conditioning system

Changsheng Wu,Zhao Zhang,FaHe Cao,Jianqing Zhang,Jianming Wang,ChĂșnan Cao
2004-01-01
Acta Metallurgica Sinica (English Letters)
Abstract:The influence of chloride or sulphur dioxide on the corrosion behavior of copper tube in the air-conditioning system was studied using scanning electron microscope (SEM), energy dispersion spectrometer (EDS) and cyclic polarization techniques. The results showed that the corrosion of copper tube are mainly caused by the SO4 2- and Cl- ions in the circulating water, and the former is mainly responsible for the general corrosion of the copper tube whilst the latter for the pitting corrosion. The different influences of SO4 2- and Cl- ions on the corrosion type of copper tube may be attributed to that the radius of SO4 2- ion is much larger than that of Cl- ion. Meanwhile the results also indicated that SO4 2- inhibits the pitting corrosion caused by Cl- and Cl- inhibits the general corrosion initiated by SO4 2- due to their competitive adsorption on the copper matrix.
What problem does this paper attempt to address?