STUDY ON PERFORMANCE OF BACKFILLED SOIL FOR VERTICAL-BURIED CLOSED-LOOP GSHP

庄迎春,孙友宏,谢康和
DOI: https://doi.org/10.3321/j.issn:0254-0096.2004.02.017
2004-01-01
Abstract:Design and performance of ground source heat pump depended on the thermal conductivity of the backfilled material. Mathematic definitions of parameters, such as density, water content and saturation, etc., describing the performance of backfilled material used for vertical-buried and closed-loop ground source heat pump (GSHP) were given, and that the main factors affecting thermal conductivity of backfilled material were density and water content. Laboratory tests based on the principle of flat probe for the measurement of thermal conductivity changing with materials selection and mix design, maintaining time and temperature were undertaken, and the results were analyzed and prepared into some curves. The experimental results showed that the bentonite is not suitable for backfilled material lonely, and it should be mixed with cement in unsaturated state. The thermal conductivity increases with decreasing water/cement ratio. It is an effective method for increasing the thermal conductivity by adding granular fillers. An increase of sand content can increase the thermal conductivity linearly. As water/cement ratio is 0.45 and ratio of sand replacement is 80%, the backfilled material has satisfactory thermal conductivity, and is thus recommended in practical engineering of GSHP.
What problem does this paper attempt to address?