EHD enhancement of boiling heat transfer in-tube utilizing different electrode configurations and polarities

Yongqi Liu,Ruiyang Li,HongLing Yu,Fagang Wang
2003-01-01
Abstract:The effect of the electrode configuration and polarity on EHD enhancement of boiling heat transfer for R-123 in a vertical tube was investigated experimentally. The test section was a vertically mounted tube-in-tube heat exchanger in which hot water flowed downwards in outer tube and the test refrigerant flowed upwards in the inner tube The cylindrical-rod and flat bar brass electrodes were applied either positive or negative high voltage, with the stainless steel tube grounded. The maximum enhancement factors of the cylindrical-rod and the flat bar electrodes applied positive high voltage were 2.1 and 2.0, respectively. The average electric field strength for the maximum enhancement of the flat bar electrode voltage was lower than that of the cylindrical-rod electrode. It was also demonstrated that the positive high voltage gave much greater enhancements and required lower average electric field strength for the maximum enhancement than the negative high voltage.