SETTING METHOD FOR CONTROL RANGE OF VOLTAGE AND REACTIVE POWER IN SUBSTATIONS

朱春明,刘明波,裴爱华,钱康龄,李芳红,霍锦强,马骥
DOI: https://doi.org/10.3321/j.issn:1000-1026.2003.08.014
2003-01-01
Abstract:The control strategy of existing voltage and reactive power controller in substation is mainly based on the nine-none diagram method. By means of discrete reactive power optimization of electric power network, a new method for computing control range setting of voltage and reactive power in substation is presented based on the active and reactive power curves of all load buses in a whole day. This method can not only trace optimal change curves of bus voltage and reactive power respectively at low-voltage and high-voltage sides of the transformer controlled, but also reduce the action number of transformer taps. Furthermore, the calculation results on the Luming power supply network of Guangzhou City and the simulation test results on the voltage and reactive power controller for substation have shown the correctness and effectiveness of proposed method.
What problem does this paper attempt to address?