VOLTAGE REGULATION STABILITY ANALYSIS OF STATCOM

LI chun,JIANG Qi-rong,WANG Zhong-hong
DOI: https://doi.org/10.3321/j.issn:0258-8013.2000.08.011
2000-01-01
Abstract:The voltage control stability of STATCOM (static synchronous compensator) was analyzed. Maximum response rate of STATCOM is always expected to meet the power system performance requirements, but its control loop might become unstable under certain circumstances. The factors influencing the stability margin of the StATCOM voltage control loop were described, including the strength of the power system viewed from STATCOM, the inherent resonance of power network, the operation point of STATCOM, the phase lock loop and the load. The phase compensation method to enhance the stability of STATCOm voltage regulating loop was presented. Theoretical analysis in frequency domain, numerical simulation and dynamic model experiment were performed.
What problem does this paper attempt to address?