New Technique For Improving The Electric Field Distribution At Hv Winding Ends Of Power Transformer
Hengkun Xie,Xile Zhang,Libo Chen,Qingfeng Xie,Zongren Peng,Xinyan Wu
DOI: https://doi.org/10.1109/icpadm.1994.413956
1994-01-01
Abstract:In this paper, the electric field at HV winding ends of UHV power transformers was analyzed by using isoparametric finite element method. The analysis indicates that the maximum electric field (Emax) in wedge-sharped oil gap close to the surface of electrostatic ring may be expressed as a function of the main insulation distance (m) between HV and LV windings, the end-insulation insulation distance (h), the radius of curvature (r) and solid insulation thickness (d) of electrostatic ring. A new type of winding end insulation system without wedge-shaped oil gap is proposed, which partial discharge inception voltage is 94% higher than that of conventional system. Another technique for improving the electric field distribution at HV winding ends is the application of SiC semiconducting coating, with which the partial discharge inception voltage of HV winding end system increases by 35%. Experimental results show that SiC coating is compatible with transformer oil at 105��C, and may be used in UHV power transformers.
What problem does this paper attempt to address?