Detection of Broken Strands and Damage Faults of High-Voltage Transmission Line Based on OTDR Technology

杨凌辉,肖嵘,季献武,任亮,贾子光,李宏男
DOI: https://doi.org/10.16136/j.joel.2013.05.017
2013-01-01
Abstract:Power transmission line,especially high-voltage transmission line plays an important role in electrical power supply system.Therefore,in order to ensure the safety of high-voltage transmission line in service,it is of vital importance to detect broken strands and damage faults of high-voltage transmission line timely and accurately.However,the commonly used methods have some problems in practical engineering.Optical time domain reflectometry(OTDR) is a commonly used instrument for fiber characterization and fault location in optical transmission systems.In this paper,a new method of detecting broken strands and damage faults of high-voltage transmission line based on OTDR technology is put forward.The theory of testing with OTDR is introduced at first.Model experimental study is conducted on a steel tube to simulate the high-voltage transmission wire,including axial tension test and horizontal shear test.Then damage simulation experiment is carried out on a section of original aluminum transmission wire.The results of the experiment demonstrate that this detecting system can be used to discriminate high-voltage transmission wire broken strands and damage faults accurately and also to estimate the crack width on the wire surface according to the level of the measured optical loss.The proposed monitoring method based on OTDR shows promising potential in broken strands and damage faults detection of high-voltage transmission line.
What problem does this paper attempt to address?