Equivalent Electric Field Strength Method Used in Corona Test of Rigid Jumpers and Fittings for UHVAC Double Circuit Tension Support

YANG Xi,LI Naiyi,LIAO Jintao,DU Jinqiao,PENG Zongren,GU Lili
DOI: https://doi.org/10.13335/j.1000-3673.pst.2013.12.042
2013-01-01
Abstract:Using finite element method the distributions of electric field on the surfaces of rigid jumpers and fittings under the conditions of actual transmission line and simplified simulated layout for the test are simulated. Using equivalent electric field strength method the corona tests on rigid jumpers and fittings for UHVAC double circuit tension support are performed, and test results show that the aluminum-tube type of rigid jumpers and squirrel cage type of rigid jumpers as well as interrelated fittings with aluminum-tube structure can meet the demand of corona test, however the interrelated fittings with the structure of squirrel cage cannot meet the demand. The corona inception field strengths at the field strength comparison points in outdoor testing field are within the range from 28.74 kV/cm to 31.38 kV/cm, and such a testing results are available for reference to other projects. It is recommended to change the clamps of partial spacers in the squirrel cage structure into the clamps of oval draught spacer in aluminum-tube structure.