Analysis on Potential Rise on UHV Oil-paper Capacitor Bushing's End Shield under Lightning Impulse Test
HU Wei,XU Zuoming,ZHANG Shiling,XIE Xiongjie,HUANG Hua,PENG Zongren
DOI: https://doi.org/10.3969/j.issn.1003-6520.2013.03.010
2013-01-01
Abstract:To analyze the reason that slight C2H2 dissolved in oil of ultra-high voltage(UHV) oil-paper capacitor bushing after lightning impulse tests,the three-ratio method was adopted to analyze the oil chromatographic data,and lower energy discharges occurring in the bushing were verified.Disassembly of the bushing indicated that the outlet wire was partly broken and there were some discharge marks on the outlet wire and pedestal.Therefore,the potential rise in the end shield was taken into account to explain the possible discharge cases.By measuring the high-frequency impedance of grounding line and current waveforms,the potential rise was estimated.The results demonstrate that the impedance of the grounding line in high frequency is much higher than that in power frequency,which is an important reason of the potential rise during the impulse test.In tests with the chopped lightning impulse,the potential rise in the end shied is up to 41 kV.It is concluded that some measures should be adopted in lightning impulse tests to avoid similar faults,including increasing the sectional area,decreasing the length of the ground lines,and taking one point to grounding.