Anti-mismatch Strategy for Volt/Reactive Power Control Between Provincial and District Power Networks under Light Load Flow Mode

ZHANG Yongjun,ZHANG Hao,TANG Jie
DOI: https://doi.org/10.13335/j.1000-3673.pst.2013.01.003
2013-01-01
Abstract:It is difficult for existing automatic voltage control(AVC) strategy to ensure fully utilization of votlage/var regulation devices in 220kV substation to meet both demands of votlage/var control from upper-and lower-level power networks,especially under light load flow operation mode the mismatching of votlage/var control between provinical and district power networks happens.Based on administration authority of provinical and district power networks,the objective of votlage/var and AVC strategy,the mechanism of mismatching of AVC-based voltage and reactive power control occurred in 220 kV substation is analyzed,and an anti-mismatching strategy that can implement coordinated control of votlage/var between provincial and district power networks is proposed.Through the characteristics of voltage and reactive power reflected by equivalent assessment model,it is revealed that the boundary voltage is the key to solve the mismatching,and the boundary voltages reflecting the voltage control states of upper-and lower-level power networks are added into local votlage correction strategy of AVC to compose a three-dimensional anti-mismatch criterion,thus under routine operation mode the votlage/var regulation devices in 220kV substation can preferentially help the lower-level power network to carry out district voltage control and under the light load flow mode the votlage/var regulation devices in 220kV substation can preferentially help the upper-level power network to execute anti-mismatch strategy for regional votlage/var control.Simulation results of actual case show that the proposed anti-mismatch strategy is effective.
What problem does this paper attempt to address?